24
Code Description
HSR Horn Strobe, Wall Mount, Snap Base,
153075100cd up to 105 dB @ 1meter
HSWC Horn Strobe, Ceiling Mount, Snap Base,
153075100cd up to 105 dB @ 1meter
Product Codes
Code HSR HSWC
Description Horn Strobes, Wall Mounted Horn Strobes, Ceiling Mounted
Standards UL Standard 464 UL Standard 464
Opperation
12/24 Vdc 15/1575/30/75/95/110/135/185 cd, 90/95/99 dB(A) 15/30/60/75/95/115/150/177 cd, 90/95/99 dB(A)
Environmental
Operating Temperature 0°C to 49°C 0°C to 49°C
Humidity (Non Condensing) 0 to 93 %RH 0 to 93 %RH
Compatibility
Suitable for use with Menvier UL fire systems Menvier UL fire systems
Technical Specification
Horn Strobe Ratings
Horn Strobe Ratings per UL 1971 & UL 464 at 24 Vdc
UL Max Current* at 99 dB(A)
24 V dc 12 V dc
Mode Regulated Voltage Range V dc 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75
HS 8.0-33.0 0.082 0.095 0.102 0.148 0.176 0.197 0.242 0.282 0.125 0.159
HSC 8.0-33.0 0.082 0.102 0.141 0.148 0.176 0.197 0.242 0.282 0.125
Horn Strobe Ratings per UL 1971 & UL 464 at 24 V dc
UL Max Current* at 95 dB(A)
24 V dc 12 V dc
Mode Regulated Voltage Range V dc 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75
HS 8.0-33.0 0.073 0.083 0.087 0.139 0.163 0.186 0.230 0.272 0.122 0.153
HSC 8.0-33.0 0.073 0.087 0.128 0.139 0.163 0.186 0.230 0.272 0.122
Horn Strobe Ratings per UL 1971 & UL 464 at 24 V dc
UL Max Current* at 90 dB(A)
24 V dc 12 Vdc
Mode Regulated Voltage Range V dc 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75
HS 8.0-33.0 0.065 0.075 0.084 0.136 0.157 0.184 0.226 0.267 0.120 0.148
HSC 8.0-33.0 0.065 0.084 0.120 0.136 0.157 0.184 0.226 0.267 0.120
All strobe models are UL dual listed - meeting
both UL1638 and UL1971 requirements. As
dual listed appliances, these weatherproof
strobes are listed for outdoor applications
under UL 1638 as well as under UL 1971, the
Standard for Safety Signaling Devices for
Hearing Impaired. With an extended
temperature range of –31°F to 150°F (-40°C to
66°C), the weatherproof appliances meet or
exceed UL outdoor test requirements for rain,
humidity and corrosion resistance while
providing multiple strobe intensity options,
including the highest strobe ratings available
for area coverage per NFPA 72 strobe spacing
tables (up to 185 candela for wall mounting and
177 candela for ceiling mounting).