38
Installation
1. Separate the two halves of the unit.
2. Drill out (or knock out) the required cable entries
in the surface mounting back-box.
3. Fit the back-box in position and pass the wires
into it.
4. Connect the unit according to the diagram below.
Note:
No addressing of the interface is required.
(See control panel operation for details).
Standard Connections
Note:
1. The end of line resistor must always be fitted, even
if the inputs are unused. Installer / service engineer
must ensure it is fitted.
2. Monitored inputs can detect open circuit, short
circuit or ground faults.
3. Output relays are volt-free contacts and are not
monitored, but most be conected to power
limited source.
4. Each I/O channel consumes a separate address
and has the facility for separate text for each
channel.
5. Recommended cable type FPLP (plenum cable),
type FPLR (riser cable), or type FPL.
Description SLC Field Wiring (input) Input 1, 2, 3 Output 1, 2, 3
Wiring Gauge 12 Max AWG 12 Max AWG 12 Max AWG
Wiring Class Class A Style 7 Class B Style C N/A
Ground Fault Impedance 0.1 ohm 0.1 ohm 0.1 ohm
Supervised, Power Limited Yes Yes Programmable
Operation
Input 1, 2, 3 Operation:
Normal Standby (Default), Alarm, Alarm, NAC
Silenced, Alarm Reset, Trouble. Trouble, Supervisory,
Drill. (Features programmable using PC site installer).
Output 1, 2, 3 Operations:
Normal Standby, Alarm.
Code Description
ULCIO351 3 Channel I/O Unit
Product Codes
Technical Specification
Code ULCIO351
Description 3 Channel I/O Unit
Standards UL864 9
th
edition
Signalling Line Circuit
Style 7, Class A, Supervised, Power Limited
Operating Voltage 24 V dc
Current 1.4 mA to 1.36 mA
Line Impedance 50 Ω
Inputs 1, 2, 3 Contact Only Initiating Circuit
Style C, Class B, Supervised, Power Limited
Voltage
(8.4 Vpp pulsed every 1 second) 8.4 (max)
Current 1 mA (max)
Line Impedance 16 Ω (max)
Trigger Resistance 5.6 kΩ
End of Line Resistor 22 kΩ
Ouput 1, 2, 3
3 Contact Set Programmable
Voltage 24 V dc to 30 V dc
Current 1 A (max, Resistive PF1)
Switching Power 33 kΩ (min)
Power Factor 1
Environmental
Operating Temperature 0°C to 49°C
Humidity (Non Condensing) 0 to 93 %RH
Physical
Dimensions (H x W x D) 180mm x 129mm x 60mm
Weight 0.28kg
Ingress Protection IP65
Compatibility
Suitable for use with Menvier analogue addressable fire systems
22k
22k
22k
5k6
5k6
5k6
-
-
-
-
-
+
+
+
+
+
LOOP
IN
OUT
ADDRESSABLE LOOP
INPUTS
OUTPUTS
Non Power Limited Circuits
Power Limited Circuits
Connect Only to a Power Limited Source
N/O
N/O
N/O
C
C
C
N/C
N/C
N/C
1
Relay1
Relay2
Relay3
2
3
ULCI0351 - 3 Channel I/O Unit
Dimensions
W
H
D
H (mm) W (mm) D (mm)
180 129 60