28
Code Description
RSSWP-2475W-FR Synchronization Strobe, Wall Mount, Outdoor, 75cd
RSSWP-2475C-FW Synchronization Strobe, Ceiling Mount, Outdoor, 75cd
WPSBB Exposed Conduit, Surface Mount
WPSBB + WPKIT Concealed Conduit, Surface Mount
WFP Back Box, Flush Mount
Product Codes
Code RSSWP-2475W-FR RSSWP-2475C-FW
Description Synchronised Strobes, Wall Mounted, Outdoor Synchronised Strobes, Ceiling Mounted, Outdoor
Standards UL1638 & UL1971 UL1638 & UL1971
Operation
Synchronisation strobe 75 cd Synchronisation strobe 75 cd
Environmental
Operating Temperature -40°C to 60°C -40°C to 60°C
Humidity (Non Condensing) 0 to 95 %RH 0 to 95 %RH
Compatibility
Suitable for use with Menvier UL fire systems Menvier UL fire systems
Technical Specification
Candela Ratings
All strobe models are UL dual listed - meeting
both UL1638 and UL1971 requirements. As
dual listed appliances, these weatherproof
strobes are listed for outdoor applications
under UL 1638 as well as under UL 1971, the
Standard for Safety Signaling Devices for
Hearing Impaired. With an extended
temperature range of –31°F to 150°F (-40°C to
66°C), the weatherproof appliances meet or
exceed UL outdoor test requirements for rain,
humidity and corrosion resistance while
providing multiple strobe intensity options,
including the highest strobe ratings available
for area coverage per NFPA 72 strobe spacing
tables (up to 185 candela for wall mounting and
177 candela for ceiling mounting).
Dimensions