44
Code Description
ULMCOM Mini Single Channel Output Unit (recognised as output unit)
ULMCOM-S Mini Single Channel Output Unit (recognised as sounder)
ULBU Mini Module Box Unit (Empty box)
Product Codes
Note:
1. Output relay are volt-free contacts and are
not monitored.
2. Recommended cable type FPLP (plenum cable),
type FPLR (riser cable), or type FPL.
Installation
1. Fit the box in position using the mounting
details below.
2. Connect the unit according to the diagram below.
3. The ULMCOM & ULMCOM-S modules can be
fitted inside a junction box.
4. Up to 3 ULMCOM & ULMCOM-S modules can be
fitted inside the FIBOX, as per diagram below.
Note:
No addressing of the interface is required.
(See control panel operation for details).
Standard Connections
Technical Specification
Operation
Normal Standby, Alarm.
Code ULMCOM and ULMCOM-S
Description Single Channel Output Units
Standards UL864 9
th
edition
Signalling Line Circuit
Style 7, Class A, Supervised, Power Limited
Current 0.322 mA (max)
Output Relay
Supervisory Programmable
Switching Voltage 24 V dc to 30 V dc
Contact Rating 1 A Resistive, pf=1 (max)
Max Line Impedance 16 Ω
Power Factor 1
Environmental
Operating Temperature 0°C to 49°C
Humidity (Non Condensing) 0 to 93 %RH
Physical
Dimensions (H x W x D) 65mm x 35mm x 18.5mm
Weight >0.1kg
Ingress Protection IP40
Compatibility
Suitable for use with Menvier analogue addressable fire systems
Description SLC Field Wiring Circuit (input) Single Channel Output
Wiring Gauge 12 Max AWG 12 Max AWG
Wiring Class Class A Style 7
Ground Fault Impedance 0.1 ohm
Supervised, Power Limited Yes Yes
Dimensions
H (mm) W (mm) D (mm)
65 35 18.5
2 self tapping screws.