DF6000 - USER MANUAL
14
1 Channel I/O device with mains rated switching capability (MIO1240)
MIO1240 is a single channel input / output unit, the output is capable of switching up to 8 A at 230 V ac.
Commonly used for applications such as door release contr
ols and plant shut down signalling the input is
monitored for open and short circuits, a specific resistance is required to activate an alarm condition, fully
open or short circuit conditions are monitored and generate a system fault signal. The input is suitable for
use as a fire signal input such as from a sprinkler flow switch, however it can also be used to monitor non
fire inputs such as an external keyswitch.
Zone monitor unit (MIU871)
MIU871 is designed to enable a zone of compatible conventional detectors and callpoints to be
connected into the DF6000 loop, it is compatible with up to 20 Menvier conventional detectors
connected via FXN520 bases. Please refer to local standards e.g. BS5839 Pt1:2002 for details of the
maximum allowable area to be covered by a single spur / zone. MIU871 fixes to a standard, deep, double
gang back box and can be either surface or semi recess mounted. When semi recessed only the front
section protrudes giving a maximum 29mm depth.
MIU871/IS
Similar to the above but the detection zone has been programmed to accept a Zener barrier and zone of
intrinsically safe detectors. End of line for this zone now becomes 6K8 and the diode in the detector base
must be removed.
Section 1 - System Installation and Design
1 channel I/O device
MIO1240
Zone monitor unit
MIU871 / MIU871/IS