DF6000 - USER MANUAL
5
Introduction
DF6000 provides all of the sophisticated features required of a leading edge analogue addressable fire
system along with the simple operation and neat installation demanded by installers and building users.
The panel can be flush or surface mounted and the generously sized metal back box allows ample
facilities for rear or top cable entries. It is available in single two and four loop versions, with or without an
integral printer.
In addition both passive and fully functional repeater panels are available.
A comprehensive range of ancillary devices is available to operate with DF6000, including optical,
ionisation, photo-thermal and heat detectors, base mounted and stand alone sounders (including an IP67
version) a loop powered beacon and a wide range of input and output interfaces.
Each of the DF6000 system components has been specifically designed to operate as part of a DF6000
system, this provides an assurance that the panel, the detectors, the interfaces and the ancillaries are all
fully compatible with each other and that the full range of system functionality is supported by each
device.
Each loop of a DF6000 panel can accommodate up to 200 addresses. To comply with EN54
requirements no more than 512 addresses should be connected to a single panel. Each panel can
indicate upto 96 zones. Panels are available with upto 4 detection loops, up to 126 panels can be
networked together to form a single system capable of operating with over 32,000 devices.
Note:
Network systems fall outside the scope of EN54.