DF6000 - USER MANUAL
25
Dependencies on More Than One Alarm Signal - Type C (option 7.12.3 of EN54 Pt 2)
The DF6000 has the facility to inhibit the operation of the output sounders, output to fire r
outing
equipment and the output of the fire protecting equipment until one more confirmatory signals are
received from different zones. This feature is programmable using DF6000 site installer software.
Alarm Counter (option 7.13 EN54 Pt 2)
The panel records the number of instances that it enters the fire alarm condition. This is abbreviated in the
touch screen by "AC" and it is displayed in the fire window at access level 2. This counter can only be
reset by the manufacturer.
Optional Auxiliary Board VDS Requirement (option not required by EN54)
This board can be connected to an extinguishing system as well as a fire brigade control panel.
This board has been tested and approved in according with DIN14661 and DIN 14675.
Input / Outputs to Fire Brigade Panel
Outputs
Output 1: Fire Protecting Equipment Operated "Extinguishing On"
This output is ON in alarm condition to indicate that the DF6000 control and indicating
equipment has operated the fire protecting equipment (option 7.10 of EN54 Pt 2).
Output 2: Fire Routing Equipment Operated "Fire Brigade Link"
This output is ON in alarm condition to indicate that the DF6000 control and indicating
equipment has operated the fire routing equipment (option 7.9 of EN54 Pt 2).
Output 3: Disablement of Fire Protecting Equipment
This output is ON to indicate that the fire protecting equipment has been disabled either by
the DF6000 control and indicating equipment or the fire brigade panel.
Section 1 - System Installation and Design