DF6000 - USER MANUAL
17
Micro Interfaces
A range of micro interfaces modules are also available:
MCIM
Is a competitively priced input module, designed to enable a Menvier panel to accept input signals from
external devices such as key switches and sprinkler flow switches. It is extremely compact
and therefore ideal for incorporation into other equipment. The maximum number of addressable MCIM per
loop is 20.
MCOM
Is a competitively priced output module, designed to enable a Menvier panel control external devices such
as door holders or access control systems. It is extremely compact and therefore ideal for incorporation
into other equipment. The maximum number of addressable MCOM per loop is 20.
MIU872
Is a compact single zone input, soft addressed, microinterface, incorporating integral short circuit isolators.
It is fully compatible with the current range of Menvier analogue fire detection panels. It is suitable for
interfacing a zone of up to 20 conventional Menvier detectors onto a Menvier analogue fire panel. It will
operate with any Menvier conventional detector in configuration with a schottky diode type base.
MCIM-C (Identified as a Callpoint)
Is a compact input module used to accept input signals from external equipment such as beam detectors,
flow switches, valve monitor switches etc. The maximum number of sounder devices per loop is 200.
MCOM-S (Identified as a Sounder)
Is a compact single channel output unit. This device is identified as a sounder output by a Menvier
addressable panel. The maximum number of sounder devices per loop is 60.
MCOM-R
Is a compact output module used to control or signal external equipment which require removal of power
for reset purposes. The maximum number of addressable MCOM-R per loop is 20.
MICM-NF
Is a compact single channel input unit. This device is identified as a non-fire input module by the Menvier
addressable panel. The maximum number of addressable MICM-NF per loop is 200. Complex cause and
effect can still be achieved using the latest site installer software without any indication on the panel.
However the action will still be seen in the event log. Ideally suited for non fire applications.
Section 1 - System Installation and Design
Micro interfaces
MCIM / MCOM / MIU872 / MCIM-C / MCOM-S / MCOM-R / MICM-NF